Equipment
Displayed Message
Error in the rapid shutdown system in String B detected
What this error means
Error 9034 indicates a communication or signal integrity issue between the inverter and the rapid shutdown device. This does not automatically mean a failed rapid shutdown unit or damaged wiring.
Root Cause Identified
Solution Implemented
In the inverter’s device parameters:
This corrected the inverter’s interpretation of rapid shutdown signaling and immediately cleared Error 9034.
Displayed Message
Grid undervoltage fast
What this error means
Error 202 is triggered when the inverter detects AC voltage that does not match its configured grid profile.
Root Cause Identified
Solution Implemented
Once updated, Error 202 cleared instantly.
Key Takeaway
On Sungrow SBSE inverters, incorrect grid standards can cause false rapid shutdown and grid fault errors. Always verify grid profile and UL category before assuming equipment failure.